content loaded
PHILIPS 71A5205500DP Image 1

METAL HALIDE BALLAST 70W M98/143 120V PHILIPS 192757

MFR Part #: 71A5205500DP
SKU #: 1116906
Brand: Signify | Philips
UPC: 400007510050
Advance 71A5205500DP Magnetic HID Ballast, HID Lamp, 70 W Lamp, 120 VAC, Pulse, 1 Ballast Factor
This product may be subject to ecological fees.
Lighting Luminaire Component and Outdoor Applications
RoHS Compliant | ANSI M98 | ANSI M143 | UL Listed | CSA Certified | UL Recognized

Advance HID Ballast, Magnetic, HID Lamp, 70 W Lamp, 94 W Wattage, 120 VAC, 0.85 A, 60 Hz Frequency, Pulse Start, -20 deg F Minimum Starting, Power Factor: 0.87, No Dimmable, 1 Lamp, Thermal Protection: Class P, 71A5205P Lamp Base, Ballast Factor: 1, ANSI M98/M143 Ballast Grade, 4.1 in L x 2.65 in W x 2.25 in H Dimensions

Philips Advance HID ballasts are available to operate the wide variety of metal halide, high pressure sodium and low pressure sodium lamps available in today marketplace. Like fluorescent, HID lamps are gas discharge lamps. Light is produced by an arc discharge between two electrodes located at opposite ends of an arc tube within the lamp outer glass envelope. The ballast is the lamp power supply; its purpose is to provide proper starting and operating voltage and current to initiate and sustain this arc. Philips furnishes 120/208/240/277 Philips Advance Quadri-Volt core and coil ballasts to allow the stocking distributor to conveniently meet the replacement and retrofit needs of customers. In addition, we now offer 120/208/240/277/480 VAC 5-TAP core and coil ballasts for the most popular applications. 5-TAP ballasts add the 480 VAC input lead to the Quadri-Volt designs. A Quadri-Volt or 5-TAP core and coil, along with the appropriate capacitor, igniter (where required), mounting bracket and hardware and installation instructions are packed in a space saving shipping carton. These "kits" eliminate the need for distributors or end users to stock loose components of single voltage ballasts for 120, 208, 240, 277 and even some 480 VAC applications, though single voltage kits for 480 VAC applications will also be available.

Product Details

Advance HID Ballast, Magnetic, HID Lamp, 70 W Lamp, 94 W Wattage, 120 VAC, 0.85 A, 60 Hz Frequency, Pulse Start, -20 deg F Minimum Starting, Power Factor: 0.87, No Dimmable, 1 Lamp, Thermal Protection: Class P, 71A5205P Lamp Base, Ballast Factor: 1, ANSI M98/M143 Ballast Grade, 4.1 in L x 2.65 in W x 2.25 in H Dimensions

Philips Advance HID ballasts are available to operate the wide variety of metal halide, high pressure sodium and low pressure sodium lamps available in today marketplace. Like fluorescent, HID lamps are gas discharge lamps. Light is produced by an arc discharge between two electrodes located at opposite ends of an arc tube within the lamp outer glass envelope. The ballast is the lamp power supply; its purpose is to provide proper starting and operating voltage and current to initiate and sustain this arc. Philips furnishes 120/208/240/277 Philips Advance Quadri-Volt core and coil ballasts to allow the stocking distributor to conveniently meet the replacement and retrofit needs of customers. In addition, we now offer 120/208/240/277/480 VAC 5-TAP core and coil ballasts for the most popular applications. 5-TAP ballasts add the 480 VAC input lead to the Quadri-Volt designs. A Quadri-Volt or 5-TAP core and coil, along with the appropriate capacitor, igniter (where required), mounting bracket and hardware and installation instructions are packed in a space saving shipping carton. These "kits" eliminate the need for distributors or end users to stock loose components of single voltage ballasts for 120, 208, 240, 277 and even some 480 VAC applications, though single voltage kits for 480 VAC applications will also be available.

Attributes

Amperage Rating.85 A
Ballast Factor1
Ballast GradeANSI M98/M143
Dimensions4.1 in L x 2.65 in W x 2.25 in H
DimmableNo
Frequency Rating60 Hz
Lamp Base Type71A5205P
Lamp TypeHID
Lamp Wattage70 W
Minimum Starting Temperature-20 deg F
Number of Lamps1
Power Factor.87
Start TypePulse
Thermal ProtectionClass P
TypeMagnetic
Voltage Rating120 V AC
Wattage94 W

Features

  • The basic ballast is the open core and coil which is most often used as a component within a lighting luminaire
  • The core and coil also forms the nucleus of Philips® advance five other ballast configurations
  • 36 uF capacitor
  • 1.4 A input current (open circuit), 1 A input current (starting), 0.75 to 1.15 A input current (short circuit), 0.85 A input current (nominal)
  • 2 x 4 core size
  • 1.65 in Dia x 2.75 in H oval capacitor
  • Thermally protected
  • Core and coil ballast with dry film capacitor
  • UL insulation class H of 180 deg C